FUEL STATIONS AND SMALL INSTALLATIONS · UNDERGROUND STORAGE

Protection is verified by measurement.

Underground fuel storage systems (SASH in Argentina) include fuel tanks and associated piping. The same protection and measurement principles apply to small industrial facilities with tanks and dispensers for their own use. This guide explains how buried metal is protected and how that protection is verified, with no prior technical knowledge required.

TWO PROTECTION METHODS

The same purpose.
Different levels of control.

Cathodic protection uses electrical current to control external corrosion of metal in contact with soil. It complements the tank coating.

Galvanic anodes

These metal components are consumed to protect steel. They do not require a rectifier, but their current output is limited and also depends on soil conditions.

They can be suitable where tanks and piping are electrically isolated from other structures and have a coating in good condition. The system must be correctly sized and measurements must confirm the protection achieved.

Impressed current

A mains-powered rectifier supplies DC to buried anodes. Its output can be adjusted to meet the protection demand of tanks and connected structures.

It requires electrical power. It provides greater current capacity and regulation when galvanic protection is insufficient.

CAPACITY FOR HIGHER DEMAND

More current available to protect connected structures.

An impressed-current system for a fuel station can deliver current equivalent to hundreds of galvanic anodes. This capacity helps meet protection demand when tanks and piping are electrically connected to earthing systems or other structures.

Anode quantity and distribution are specified according to installation conditions, required current and intended service life.

Both systems need monitoring.

Both galvanic anodes and impressed-current systems require periodic measurements. Having no electrical power supply does not remove the need to verify protection. SELEC provides annual inspection and certification services for both systems.

CATHODIC PROTECTION COMPONENTS

A circuit to protect the whole installation.

Select a component in the diagram or use the buttons to learn what it does.

Impressed-current cathodic protection of a tank and piping at a fuel station SurfaceSoil Dispenser Steel tankMetal piping Negative (−)Positive (+) Anodes Protection current through the soil DC+−Rectifier

Conceptual diagram, not to scale. Anode spacing, locations and connections are defined in the engineering for each installation.

EXPLORE THE COMPONENTS

Rectifier

Converts mains power to DC and allows output adjustment to meet protection demand. The positive terminal connects to the anodes and the negative terminal to the metal structure being protected.

Possible electrical connections between tanks and piping A metal tank vent rises beside a column and may be electrically connected through conductive fixings. Metal piping reaches the dispenser, which has an earthing connection. The highlighted contacts must be assessed at each installation. Soil Metal fixings Tank vent Column Dispenser Earthconnection Steel tank and metal piping
Highlighted points show possible connections. Electrical continuity is verified through field measurements.

THE SYSTEM IS NOT ALWAYS ISOLATED

Current can flow beyond the intended structures.

Metal vents can connect a tank electrically to their supporting columns through conductive fixings. Connections can also exist through metal piping and the dispenser's earthing system.

A metal connection can electrically link the tank to earthing networks, pipes or other buried elements. The system must then protect a larger surface than originally intended.

If the anodes cannot supply enough current, part of the installation may be inadequately protected. Changes to connections can also alter a previously effective system.

This is why connections are assessed and actual protection is measured. Never disconnect earthing or safety connections to improve a reading: the solution must reconcile cathodic protection with the station's electrical safety.

EACH TANK IS ASSESSED

Measure the tank potential relative to the soil.

Potential is a voltage difference. Measuring it helps determine whether the metal receives sufficient protection.

Station surfaceSoilmVMeasuring instrumentSteel tankTank connectionPortable electrodePlaced on the surface
Conceptual diagram: component locations and quantities are specified for each installation.

A portable reference electrode

The instrument connects to the tank metal and a reference electrode—usually copper/copper sulphate—placed on the station surface over each tank.

Several representative measurement locations are used over each tank. A reading beside an anode does not replace this survey.

A record for each structure

Tanks, piping and test points are identified. Electrode position and system conditions are documented so results can be interpreted and compared.

Measurement location can change the conclusion.

An electrode inside the anode backfill can register an artificially more negative potential due to the nearby electrical field. That reading does not demonstrate tank protection. The reference must be reliable and its location representative of the structure being assessed.

LOOK BEYOND THE DISPLAYED VALUE

A favourable ON reading alone does not demonstrate protection.

ON · Current applied

The reading includes voltage drop in the soil. It can suggest protection the tank does not actually have: reaching −850 mV ON is not, by itself, sufficient to conclude that it is protected.

Instant OFF · Current interrupted

The reading is taken immediately after current interruption, before appreciable depolarisation. It allows assessment of polarised potential while reducing the influence of voltage drop in the soil.

−850 mV: how the value is obtained matters. To apply the −850 mV polarised-potential criterion relative to copper/copper sulphate, the instant-OFF value must be equal to or more negative than this value. This is different from reaching that number ON. Other assessment criteria exist; their application requires consideration of the system and measurement conditions.

Interruption must account for the current sources affecting the measurement. Connected galvanic anodes and other sources can continue to influence the reading; switching off one rectifier does not always provide a representative OFF value.

FROM DATA TO DECISIONS

SELEC verifies protection tank by tank.

Assessment and corrective action.

We identify each tank and survey point, assess existing connections and document potentials, measurement conditions and the criterion used. The report shows which structures are protected and which require action. Conclusions rely on the complete survey, not a single favourable value.

If protection is insufficient, the required corrective action is defined. When current demand exceeds galvanic-system capacity, an impressed-current system is designed and its performance verified during commissioning.

Measurements and criteria based on international standards.

We apply the measurement techniques and protection criteria of the relevant NACE/AMPP standards: SP0169 (formerly RP0169) for buried metal piping, SP0285 for underground tank systems and TM0101 for their measurement techniques.

Argentina's Secretariat of Energy protocol for SASH installations requires recognised standards, such as NACE, and records of ON and instant-OFF potentials at acceptance to verify compliance with the adopted standard.